WIRE
Use the right wire for each part of the job. The wire needs to last as long
as the other equipment. A common mistake is to use what ever is available at the
hardware store to wire solar panels and batteries. A few years later when the
insulation starts flaking off the wire, the whole job has to be redone.
Comparing Common Wire types for Solar:
Wire Type |
Outer Insulation |
Outdoor Rated |
Flexibility |
Common Uses |
Available from: |
NMB |
Yes |
No |
No |
Indoor
House wiring |
Hardware store, etc. |
UF |
Yes |
Yes |
No |
Outdoor
circuit wiring |
Hardware store, etc. |
USE |
No |
Yes |
Yes |
Buried power lines |
Electrical supply |
THHN |
No |
No |
Yes |
In
conduit |
Hardware or Electric supply |
TC |
Yes |
Yes |
Yes |
Solar
module wiring |
Solar dealer |
outdoor rated wire is rated to be buried
directly in the ground, or to be exposed to direct sunlight. Any wire exposed
to possible physical damage should be in conduit (generally up to 6 ft out of
the ground). Wire Size: wire is sized by American
Wire Gauge AWG. Smaller numbers indicate larger wire up to 0000 or 4/0 ( pronounced
"Four ought"). Larger wire is listed in MCM, which is normally only
used in commercial work. Other countries use metric sizing which measures wire
by its cross sectional area of copper in sq. millimeters. Comparing
Common Wire Sizes:
American Wire Gauge |
Metric (Sq. MM) |
Max. Current (example only!)** |
Example Uses |
22 |
|
2 |
Telephone |
18 |
|
5 |
Meter |
14 |
|
15 |
Lighting |
12 |
|
20 |
House circuits,
solar interconnects |
10 |
|
30 |
pump
wiring, portable generator |
8 |
|
40 |
|
6 |
|
60 |
solar array to house |
4 |
|
80 |
small Battery cables |
2 |
|
100 |
small house service |
1 |
|
125 |
|
0 (1/0) |
|
150 |
|
00
(2/0) |
|
175 |
Battery
Cables |
4/0 |
|
250 |
Large Inverter
cables |
250 MCM |
|
400 |
Main feed
to building | ** Choosing the right wire size depends
on numerous factors: Continuous Amps, surge amps, volt drop, cost, insulation
rating, temperature, # wires in conduit, wire type, breaker or fuse type, etc.
See our wire selector spreadsheet for guidance,
use the latest NEC book to get closer, and consult with your electrician and inspector
for the final say on what wire size is correct. Copper Vs. Aluminum (Cu,
Al) In solar work, most wiring is done in copper. Aluminum cannot carry
as much current for its size, has greater resistance, and most importantly is
prone to corrosion. Aluminum is however cheaper, so for very long runs ( over
150 ft) of very heavy gage wire (2/0 or larger) Aluminum can be a good choice.
It comes in twisted 3 wire or 4 wire bundles known as URD. It must be connected
using Al rated connectors, completely isolated from copper wires or connectors,
and all exposed Al should be coated with special aluminum oxide inhibitor (NoAlox). Flexibility:
wire flexibility is important when wiring solar modules, especially if using
a moving tracker. Stiff wire could prevent the tracker from moving properly, and
over time strain harden and break. Also, generators or any location subject to
movement or vibration should use flexible wire. Standard Stranded THHN wire is
still so stiff it can strain the posts on batteries and inverters. Flexible wire
is also easier to pull and work with, but it can be harder to make good connections.
Solid core wire works much better for wiring household outlets for instance. Wire
flexibility is rated in Strand Count - the number
of separate strands of copper that make a single cable.
Wire |
Strand Count |
Flexibility |
Good Use |
Proper Connectors |
Wire |
Bad
Use |
Improper
Connectors |
It is also important to use the right connector with the stranded wire.
Stranded wire doesn't work well with household outlets for instance, and very
finely stranded cable (welding cable) can over compress and tear in some mechanical
lugs (like in normal AC load centers).Solid core wire on the other hand, is very
difficult to properly crimp. Connectors. Remember, a circuit is only
as safe as its weakest link. All connections need to be rated for the same high
DC amperage and extreme conditions that the wire is rated for. A single weak connection
can disable an entire system with dozens of connections. Many ways of connecting
one wire to another exist. Some are permanent like soldering, or crimping, some
are reversible like mechanical connectors or wire nuts. Good design allows connectors
to be accessed later (inside junction box, with removable cover) for inspection,
testing, and retightening. Wire Nuts: are cheap, and work well
for #6 and smaller coarse stranded wire. Mechanical Connectors: consist
of a metal barrel or bar with holes in it. A screw tightens and pinches the wire
in the barrel. A screw driver or hexhead driver are used to tighten the connection
to its rated torque. Examples include the Main lugs and neutral bar in Load
centers, the connectors on breakers, insulated blocks, Euro strips, etc. What
happens when you have a bad connection: If not enough metal is touching metal,
or the connection is loose, or corroded, you have a Bad connection. Bad connections
will not allow electricity to flow freely. Because they cause resistance, some
voltage is lost in the connector as heat. This voltage drop can cause poor system
performance, and other equipment to malfunction. Bad connections do not improve
with time. The heat and possible arcing, along with moisture and corrosion cause
the resistance to increase. If the connector continues to overheat, the insulation
on the wire can melt back and even catch on fire. The Difference
between a short and a bad connection: A short actually reroutes electricity,
like a power wire touching grounded metal, or a wrench connecting the positive
and negative battery terminals together. Conversely, a bad connection restricts
or stops electricity. A bad connection can then come loose and touch something
it shouldn't and thus become a short too!
|
Good Connection |
Bad Connection |
Wire Nut |
Each wire is close to equal length in connection, Wires
twisted until they begin wrapping around each other past the connector.
Enough copper is stripped off to make a couple of bare twists without
sticking bare metal outside the wire nut. |
Some bare wire wrapped around the insulation of the
other wire, wire not twisted enough, wrong size connector used, wire
nut loose, bare wire sticking beyond the wire nut. Wires can be pulled
out |
Mechanical Lug |
Correct wire is inserted completely, insulation is trimmed
visibly back from connection, connector is tightened to listed torque.
All strands inserted completely through connector |
Pulled loose, not enough metal in connection, insulation
pinched in connection, not tightened, over tightened and damaged connector
or wire. Too finely stranded wire used or some strands straying out
of connector. |
Crimp Lug |
Same rules as above, but lug must match wire size, and
the proper crimp tool is used. |
Wrong sized lug, crimp made with pliers, hammer, or
mismatched crimp tool, wire is loose or can pull right out of connection |
Split Bolt |
Wires are stripped back for entire surface of
split bolt, Tightened with two wrenches,(hard to use torque wrench) Insulated
completely with soft cold shrink tape first, then wrapped with regular electrical
tape after |
Wires not stripped enough, Aluminum and copper touching
without metal separator in between, Not tightened enough(bad connection),
not taped enough (short to metal box) |
Finding Torque
specs for different lugs can be tough, since they change depending on the wire
size too. Try not to guess at torque; manufacturers use different alloys of metals
for greater conductivity that are much softer than a regular bolt, and take far
less torque. Don't wait till you have broken a main lug off from overtightening,
Check that Torque! Example Torque Spec.s:
Ft-lb.s |
Inch- Lb.s |
Tool |
Lug Type |
3 |
36 |
screw driver |
small screws on light switch |
5 |
60 |
3/8"
drive Inch-Lb. Torque wrench |
Main lugs Outback Inverter |
12 |
144 |
3/8"
drive Inch-Lb. Torque wrench |
Main lugs Xantrex Inverter |
21 |
250 |
3/8"
drive Inch-Lb. Torque wrench w/ hex attachment |
Main Lugs in Large AC load Center |
You'll need a torque wrench
that reads in Inch- Lb.s. 1 in-lb. of torque is 1 lb. of force applied to
1" of leverage. 1 foot-lb. then is 1 lb exerted against a 1 ft lever
(like a wrench) around a pivot point (the screw). Finally, 12 inch-lbs = 1 ft-lb. Crimp
Lugs: are copper tubing or alloy that is pinched permanantly onto the wire
by a press or hammer jig. Use the right size crimp with right wire, and the right
crimping tool. If you don't have the right tool get one, or use a different type
of connector. Steps to a Good Connection:
1) Start with the right connector and wire. 2) Strip insulation from wire
so that bare wire is just visible outside of the connector. For example if a lug
is 1/2" deep, strip about 5/8" of wire so that 1/16" of bare metal
is visible on either side of the connector. Some connectors have a strip guide
marked on them to show proper length. 3) Once the insulation is removed,
protect the bare metal from damage, make sure all strands of copper are in the
connector. 4) Tighten the connector to the proper torque, use the proper crimp
tool crimped in the middle of the lug, or twist wire nuts until the wires wrap
around each other. 5) heat shrink over the connection, or wrap it in electrical
tape if using uninsulated crimps. Switches need
to be rated to the same conditions as the rest of the circuit. Warning:
Regular AC light switches should NOT be used for DC! The 50 cent silent switches
from the hardware store eventually will burn in the "ON" position and
cannot be turned off! They are marked "AC only" for a reason. DC
rated switches are much more expensive and only available through solar dealers.
|